SENSOR PROGRAMMING - STEP 4
Optional
programming features are available to adjust the sensor and display performance. Review the information below
for your
application.
|
Lockout |
|
A lockout feature is available to prevent changes to the
programming of the sensor. To activate, press the "Mode"
and Arrow Down" keys simultaneously. The letters
"LOC" appear blinking on the display indicating the sensor
programming features are now locked preventing any unwanted changes.
To unlock the programming features, repeat the above procedure. |
 |
|
Zero Reset |
|
This feature
is a manual calibration to reset your beginning value to zero. Press
the "Mode" key and hold for 3 seconds to reset the sensor. |
 |
|
Peak Value and Bottom Value |
|
To periodically check the high value of the system, press
the "Arrow Up" key one time. "PE" momentarily
appears on the display followed by the high value of the system
blinking. This feature automatically stops after 3 seconds. To
check the low value of the system, repeat this procedure by pressing the
"Arrow Down" key and "bo" will appear on the display. |
 |
|
Display Refresh Setting/Output Response Time Interval |
| This feature updates
the value on the display in increments of 0.1 seconds beginning with 0.1
to 1 second (factory setting is 0.3 sec.). This feature can be
useful in cases where vacuum leakage of porous products makes it difficult
to read the display. To change the display refresh time, press the
"Mode" key 6 times (the number 6 will appear on the display) and
wait 3 seconds. "dsp" and "0.3" will alternate
on the display. Press the "Arrow Up" or "Arrow
Down" keys to change the display refresh time. Press the
"Mode" key to enter and store this value.
The programming sequence defaults to output response
time ("AUE and "1") which will alternate on the
display. The sensor response time 2.5 milliseconds which corresponds
to the factory output setting of "AUE" and "1". This
feature can be used to stabilize inconsistent outputs resulting in
variances in work piece porosity or correspond with time of the overall
system response if necessary. The options are as follows: |

|
Display Number
1
16
64
512 |
|
Response Time
2.5 milliseconds
40 milliseconds
160 milliseconds
1280 milliseconds |
| The display number
is a multiplier of the response time. To change the response time,
press the "Arrow Up" or "Arrow Down" keys. Press
the "Mode" key to enter and store this value. The word
"End" will appear signifying the completion of this programming
feature. |
Display
Peak Value, Bottom Value, or their Difference |
| Activating
any of these features will display the Peak Value Only,
Bottom Value Only, or the overall Difference between the
Peak and Bottom Value Only. This feature
facilitates a "quick" check of the system
performance. The default factory setting of this
feature if "Off". To begin this
programming, press the "Mode" key 7 times (the
number "7" will appear on the display) and
wait 3 seconds. "Pb" and "Off"
will alternate on the display. To activate this
feature press the "Arrow Up" or "Arrow
Down" key. "Pb" and "On"
will alternate on the display. Press the
"Mode" key to enter and store this
information. If this feature is not activated, the
word "End" will appear signifying the
completion of the programming sequence.
If
activated, the programming sequence defaults to a
"sampling time" function of this
feature. The sampling time is the frequency the
peak value, bottom value, or difference between peak and
bottom value is displayed. This is the interval
the actual pressure is sampled. "Pbt"
and "10" will alternate on the display.
The sample time range is from 2 seconds to 99
seconds. Press the "Arrow Up" or
"Arrow Down" keys to record sample
frequency. Press the "Mode" key to enter
and store this value. The programming sequence
defaults to the pressure range to be displayed. :Pbd"
and "PE" will alternate on the display.
Select the pressure to be displayed; PE (peak value), bo
(bottom value), or du (difference between peak and
bottom values) by pressing the "Arrow Up" or
"Arrow Down" keys. Press the
"Mode" key to enter and store this
information. The word "End" will appear
signifying the completion of the programming sequence.
|
|
|
|
Automatic Teach Mode |
Automatic teach
mode function sets OUTPUT 1 in the hysteresis mode and OUTPUT 2 in the
Window Comparator mode automatically. The switch point H-1 is 60% of the
maximum vacuum level displayed during the setup operation of the system.
To begin the programming sequence, press the "Mode" 5 times. The
number "5" appears on the display. After 3 seconds, "AUT"
will blink on the display. Begin and cycle the vacuum system allowing the
vacuum to reach the maximum level. It is important to maintain this level
during the setup. The switch point H-1 will be automatically set to 60% of
the maximum vacuum level precluding the need to manually set switch point
"H-1". The hysteresis range is automatically 5% of the switch
point recorded by the sensor. While continuing the vacuum cycle, press the
"Mode" key to enter and store this information. The programming
sequence defaults to establishing the bottom value of the vacuum cycle
during the blow-off or vacuum release cycle. Typically this value is zero,
but any other value will be subtracted from the maximum vacuum level to
determine H-1.
|
 |
| Hysteresis
Mode: H-1 = (peak vacuum level – bottom vacuum level) x 60%, h-1
= (H-1) x 5%
Window Comparator Mode: A-2 = (H-1) x 80%,
B-2 = Peak Value x 80%
|
| After
the blow-off or vacuum release cycle is complete, press the
"Mode" key to enter and store this information. The sensor will
automatically calculate "H-1/h-1" and "A-2/B-2" based
on the system performance.
The programming sequence defaults to the
"auto-surveillance" feature to monitor the peak vacuum level of
the system. "AL" and "off" will alternate on the
display. This option provides signal "OUTPUT 2" along with
"OUT 2" LED indication if the peak vacuum level of the system is
not reached over a consecutive number of surveillance’s programmed. To
activate or deactivate this function, press the "Mode" key one
time. To exit this function, press the "Mode" key again and the
word "end" appears completing the programming sequence. If the
"auto-surveillance" function is activated, "ALn" and
"1" will alternate on the display. Press the "Arrow
Up" key to select the number of consecutive peak values to be
monitored before providing an output alarm (1-100 times). Press the
"Mode" key to enter and save this information. The word
"end" will appear signaling the end of the programming sequence. |
|
Special Display Features |
The special display features are
a series of display options that visually differentiate the display when
the output signals are "ON". Press the "mode" key 8
times (the number "8" will appear on the display) and wait for 3
seconds. "dSF" and "off" will alternate on the
display. To access the special display features, press the "Arrow
Up" or "Arrow Down" keys until "dSF" and
"ON" alternate on the display. Press the "Mode" key to
proceed to the different options. "FNC" and "Ib" will
alternate on the display. Display types and descriptions are shown below.
|
 |
| |
|
|
1b: |
|
This display feature
blinks intermittently when OUTPUT 1 signal is "ON" and is normal
when OUTPUT 1 is "OFF". |
|
|
1d: |
|
This display shows a
special screen when the OUTPUT 1 signal is "OFF". When the
OUTPUT 1 signal is "ON" the pressure value is continuously
displayed. |
 |
|
2b: |
|
This display feature
blinks intermittently when OUTPUT 2 signal is "ON" and is normal
when OUTPUT 2 signal is "OFF". |
|
|
2d: |
|
This display shows a
special screen when the OUTPUT 2 signal is "OFF". When the
OUTPUT 2 signal is "ON" the pressure value is continuously
displayed. |
 |
|
Off: |
|
Energy saving
feature can be activated to reduce current consumption. |
|
|
AL: |
|
Display confirmation
option for digital input sensors only. Digital input option resets the
display value to zero for calibration purposes. "AL" will be
displayed after each input signal is received for confirmation. |
|
| Press the
"Arrow Up" or "Arrow Down" keys to scroll through the
special display features. Press the "Mode" key to activate and
store the desired display. This completes the programming sequence. |
|