Home     Distributors Only     Contact Us      Need Help?
 

Return to Programming Home
Go to Step: 1 2 3 4  Next Step>

         SENSOR PROGRAMMING - STEP 1

DEFINITIONS
A. Output Setting Normally Open or Closed:
The output can be set to turn "on or off" up to the pressure switch point by the user. The output is NPN (Sinking Voltage) or PNP (Sourcing Voltage). Typically, the system PLC will dictate the need for NPN or PNP outputs and the system programmer determines the logic of the output setting N.C. or N.O.

B. Units of Measure:  Units of measure can be selected on the sensor display.   Below is a chart for the available units of measure based on sensor type.  Units of measures available are as follows:

VACUUM: mmHg (-Hg), inHg (-iH), -Pa (kPa), -bA (-bar), Ps (-PSI), mH (mmH2o), iH (inH2o)

POSITIVE PRESSURE: Ps (PSI), Fg (kgf/cm2), bA (+bar), Pa (+kPa)

Display Unit of Measure

Sensor Type

P2 V2 L2 R2 P3 V3 L3 R3 D4 H4 V4 201 V9 R9
-Hg (mmHg), -iH (inHg), -Pa (kPa), -bA (bar)   X       X             X  
PA (Mpa), bA (bar), Fg (kgf/cm²), PS (PSI) X       X                  
PS (PSI, Fg (kgf/cm²), bA (bar), PA (kPa)     X X     X X       X X X
PA (kPa), mH (mmH2O), iH (inH2O)                 X X X      
 

C. Easy Mode Output Switch point:  This feature SHOULD BE THE FINAL OPTION after completing all the programming sequences 1-8. If activated, the sensor will only allow adjustments to the switch points "H-1/H-2". This is to minimize the time required to make switch point adjustments. The hysteresis values "h-1" and "h-2" previously will not be changed.

 

hysteresisnew.jpg (136668 bytes)

windowcomp.jpg (136953 bytes)

 PROGRAMMING PROCEDURE

To initiate this programming procedure press the "MODE KEY" and "ARROW UP KEY" simultaneously.  Press the "MODE KEY" to enter the information and forward the programming to the next setting.  Continue until the word "END" appears.

A. OUTPUT SETTING OPEN OR CLOSED 

The sensor has two independent outputs (NPN or PNP) that  can be programmed "ON" (closed)  or "OFF" (open) up to the switch point setting  (H-1/H-2 or A-1/A-2).  The factory setting  "OU1" and "N.O." will alternate on the display.  To change the output from the factory setting,  press the "Arrow Up" key one time only.  "OU1" and "N.C." will continue to alternate on the display with the Output 1 indicator LED "ON".  To enter and store this selection press the "Mode" key.

MODE KEY AND ARROW UP KEY

The programming sequence defaults to "OU2" (output 2) and "NO" (normally open), which will alternate on the display.  Repeat the procedure to set Output 2.  Again, press the "Mode" key to enter and store this information.

B. UNITS OF MEASURE 

DISPLAY TYPE SENSORS offer a selectable unit of measure.  The programming sequence will default to the "units of measure" selection.  The factory set unit of measure "-Pa" (Pascal) will appear on the display. To select another unit of measure,  press the "Arrow Up" or "Arrow Down" key one time.  Continue with this procedure until the desired unit of measure is displayed.  To enter the selection, press the "Mode" key one time and this information will be entered and stored in the sensor.

C. Easy Mode Switch Point Changing:
To activate this feature, press the "Arrow Up" or "Arrow Down" key. "E5Y" and "ON" will alternate on the display. To exit, press the "Mode" key one time and the easy mode feature is activated, the word "End" will appear.

If activated, adjust the previously set switch point value "H-1", press the "Mode" key one time. "H-1" and "A Number" previously set will alternate on the display. To adjust this number press the "Arrow Up" or "Arrow Down" keys. Press the "Mode" key to enter this value and the sensor will default to "H-2" and "A Number" previously set which will alternate on the display. Press the "Arrow Up" or "Arrow Down" keys to change the value if necessary. To exit this feature, press the "Mode" key one time and this information will be entered and stored in the sensor.

 Go to Step: 1 2 3 4  Next Step>

 
 

 

 

Parker Hannifin Corporation
Pneumatic Division North America
8676 East M-89 Richland, MI 49083
Toll Free U.S.A.

Phone: 888-266-8221
      Fax: 888-266-8223
Local and International
Phone: 1-616-629-2530
Fax: 1-616-629-2514
Email: assmith@parker.com